Smokeproof enclosure (original) (raw)

About DBpedia

In building safety and construction, a smokeproof enclosure is a type of that has been designed to keep out smoke (and other ) in the event of a fire, so that building occupants may more safely exit the building. Rather than entering the stairwell directly from the building interior, one enters a smokeproof enclosure by means of an open-air balcony or alternatively, a so-called open vestibule, and proceeds thence, to the stairwell itself. The way that the balcony or vestibule is ventilated divides smokeproof enclosures into two basic types: mechanically ventilated which is not actually a smokeproof enclosures, where the vestibule and stairwell are ventilated by mechanical equipment, and naturally ventilated open air smokeproof enclosures where the open balcony or vestibule [or the stairwe

Property Value
dbo:abstract In building safety and construction, a smokeproof enclosure is a type of that has been designed to keep out smoke (and other ) in the event of a fire, so that building occupants may more safely exit the building. Rather than entering the stairwell directly from the building interior, one enters a smokeproof enclosure by means of an open-air balcony or alternatively, a so-called open vestibule, and proceeds thence, to the stairwell itself. The way that the balcony or vestibule is ventilated divides smokeproof enclosures into two basic types: mechanically ventilated which is not actually a smokeproof enclosures, where the vestibule and stairwell are ventilated by mechanical equipment, and naturally ventilated open air smokeproof enclosures where the open balcony or vestibule [or the stairwell] has openings directly to the outside of the building. This is the only type of the original concept of a smokeproof tower (i.e.: smokeproof enclosure). Under United States building codes, the stairwell of a smokeproof enclosure must have walls with a 2-hour fire resistance rating and vestibule doors (if provided) with a 1.5 hour fire resistance rating. The Life Safety Code states that such stairwells be "approved systems with a design pressure difference across the barrier of not less than 0.05 in. water column (12.5 Pa) in sprinkled buildings and 0.10 in. water column (25 Pa) in non-sprinkled buildings".Approved, in the Life Safety Code, means the committee didn't want to 'decide' so, left it up to someone else to decide a particular issue. In the so-called mechanically ventilated smokeproof enclosures, the stairwell is positively pressurized relative to the rest of the building. This ensures that even when access doors are opened, smoke will not enter the stairwell. Of course, a higher pressure within a stairwell makes it harder to open doors from the building interior to the enclosed vestibules and to the enclosed stairwell. The Life Safety Code requires that the pressure differential across the barrier not be so great as to prevent the door from opening with a force of 30 lbf (133 N) at the door knob or handle. These 'pressurization' problems are, of course, non-existent with naturally ventilated smokeproof enclosures. The fans and air ducts used to pressurize the stairwell are life-critical systems, and are required to be enclosed in non-combustible, likewise two hour rated, construction. (For fully sprinkled buildings, the required rating is just one hour.) The fans must be connected to an emergency power supply, and capable of both automatic activation by various fire and smoke detectors, and of manual activation by a central command post or by the actuation of a general fire alarm. (en)
dbo:wikiPageExternalLink http://csemag.com/search/search-single-display/rethinking-the-smokeproof-enclosure/8f16a76976.html%7Cjournal=Consulting
dbo:wikiPageID 33416468 (xsd:integer)
dbo:wikiPageLength 6074 (xsd:nonNegativeInteger)
dbo:wikiPageRevisionID 1070713274 (xsd:integer)
dbo:wikiPageWikiLink dbr:Pound_(force) dbr:Inch_of_water dbr:Life_Safety_Code dbr:Positive_pressure dbc:Stairways dbr:Fire_safety dbr:Pascal_(unit) dbc:Safety_codes dbr:Newton_(unit) dbr:Air_duct dbr:Combustion_product dbr:Exit_stair
dbp:wikiPageUsesTemplate dbt:Citation_style dbt:Cite_book dbt:Cite_journal dbt:Cleanup dbt:Firefighting-stub dbt:Multiple_issues dbt:Orphan dbt:Refbegin dbt:Refend dbt:Reflist dbt:Sfn
dct:subject dbc:Stairways dbc:Safety_codes
gold:hypernym dbr:Stairwell
rdf:type yago:WikicatStairways yago:Artifact100021939 yago:Object100002684 yago:PhysicalEntity100001930 yago:YagoGeoEntity yago:YagoPermanentlyLocatedEntity yago:Stairway104298308 yago:Way104564698 yago:Whole100003553
rdfs:comment In building safety and construction, a smokeproof enclosure is a type of that has been designed to keep out smoke (and other ) in the event of a fire, so that building occupants may more safely exit the building. Rather than entering the stairwell directly from the building interior, one enters a smokeproof enclosure by means of an open-air balcony or alternatively, a so-called open vestibule, and proceeds thence, to the stairwell itself. The way that the balcony or vestibule is ventilated divides smokeproof enclosures into two basic types: mechanically ventilated which is not actually a smokeproof enclosures, where the vestibule and stairwell are ventilated by mechanical equipment, and naturally ventilated open air smokeproof enclosures where the open balcony or vestibule [or the stairwe (en)
rdfs:label Smokeproof enclosure (en)
owl:sameAs freebase:Smokeproof enclosure yago-res:Smokeproof enclosure wikidata:Smokeproof enclosure https://global.dbpedia.org/id/4vBpm
prov:wasDerivedFrom wikipedia-en:Smokeproof_enclosure?oldid=1070713274&ns=0
foaf:isPrimaryTopicOf wikipedia-en:Smokeproof_enclosure
is dbo:wikiPageRedirects of dbr:Pressurised_staircase dbr:Pressurized_stairwell dbr:Stairwell_pressurization
is dbo:wikiPageWikiLink of dbr:Pressurised_staircase dbr:Pressurized_stairwell dbr:Stairwell_pressurization
is foaf:primaryTopic of wikipedia-en:Smokeproof_enclosure