Steam Trap Selection Guide (original) (raw)

A steam trap is a self contained valve which automatically drains the condensate from a steam containing enclosure while remaining tight to live steam, or if necessary, allowing steam to flow at a controlled or adjusted rate. Most steam traps pass non-condensable gases like air while remaining tight to live steam.

A steam trap should

There are three primary categories of steam traps:

Popular traps in these categories includes the float steam trap, the thermostatic steam trap, the inverted bucket steam trap and the thermodynamic disc steam trap. Which one is preferred depends on the application.

A steam trap prime missions is to remove condensate and air preventing escape of live steam from the distribution system. The steam trap must adapt to the application. A disc thermodynamic steam trap should never be used together with a modulating heat exchanger - and a floating ball steam trap may be overkill for draining steam pipes.

The table below can be used as a short guide for the selection of steam traps:

Steam Trap Selection Guide

Type of Steam Trap Operation Normal Failure Mode
No or little load Light Load Normal Load Heavy Load
Float & Thermostatic No action Usually continuous. May cycle. Usually continuous. May cycle. Continuous Closed
Inverted Bucket Small dribble, may leak steam with very little condensate load May dribble Intermittent Continuous Variable
Bi-metal Thermostatic No action Usually dribble action May blast at high pressures Continuous Open
Impulse Small dribble Usually continuous with blast at high loads Usually continuous with blast at high loads Continuous Open
Thermodynamic Disc No action Intermittent Intermittent Continuous Open

Thermostatic Steam Traps

There are two basic designs for the thermostatic steam trap, a bimetallic and a balanced pressure design. Both designs use the difference in temperature between live steam and condensate or air to control the release of condensate and air from the steam line.

In a thermostatic bimetallic trap it is common that an oil filled element expands when heated to close a valve against a seat. It may be possible to adjust the discharge temperature of the trap - often between 60 oC and 100 oC.

This makes the thermostatic trap suited to get rid of large quantities of air and cold condensate at the start-up condition. On the other hand the thermostatic trap will have problems to adapt to the variations common in modulating heat exchangers.

Float Steam Traps

In the float steam trap a valve is connected to a float in such a way that a valve opens when the float rises.

The float steam trap adapts very well to varying conditions as is the best choice for modulating heat exchangers, but the float steam trap is relatively expensive and not very robust against water hammers.

Inverted Bucket Steam Trap

In an inverted bucket steam trap a leverage system multiplies the force provided by the bucket to open a valve against the pressure. The bucket is open at the bottom and robust against water hammers.

Thermodynamic Disc Steam Traps

The thermodynamic trap is an robust steam trap with simple operation. The trap operates by means of the dynamic effect of flash steam as it passes through the trap.

Condensate Pumping

High temperatures and danger of impeller cavitation is the major challenge for condensate pumping in steam systems.

Sizing Steam Pipes (lb/h)

Steam is a compressible gas where the capacity of a pipe line depends on the size of the pipe and the steam pressure.

Steam Pipes - Sizing

Sizing of steam pipe lines - major and minor loss in steam distribution systems.