Treatment of a Legionella pneumophila-Colonized Water Distribution System Using Copper-Silver Ionization and Continuous Chlorination | Infection Control & Hospital Epidemiology | Cambridge Core (original) (raw)
Abstract
The detection in April 1997 of a case of nosocomial legionellosis in our hospital led to the discovery that both our hot- and cold-water circuits were heavily colonized with Legionella pneumophila. Conventional methods for eradication of the organisms were unsuccessful, so a copper-silver (Cu-Ag) ionization system and a continuous chlorination system were installed. Five months later, the number of colonized sites decreased from an initial 58.3% to 16.7%.
References
Muraca, PW, Yu, VL, Goetz, A. Disinfection of water distribution systems for Legionella: a review of application procedures and methodologies. Infect Control Hosp Epidemiol 1990;11:79–88.Google Scholar
Best, M, Yu, VL, Stout, J, Goetz, A, Muder, R, Taylor, F. Legionellaceae in the hospital water-supply. Epidemiological link with disease and evaluation of a method for control of nosocomial legionnaires' disease and Pittsburgh pneumonia. Lancet 1983;2:307–310.. JAMA 1988;259:2423–2427.CrossRefGoogle ScholarPubMed