Prometheus exporter which retrieves stats from a modbus tcp system and exports them via HTTP for Prometheus consumption.

Scrape sequence

Reproduce diagram

Go to: https://bramp.github.io/js-sequence-diagrams/

Note right of Prometheus: promehteus.yml \n --- \n target: Modbus-TCP-10.0.0.5 \n subtarget: Modbus-Unit-10 \n module: VendorXY
Prometheus->Exporter: http://xxx.de/metrics?target=10.0.0.5&subtarget=10&module=vendorxy
Note right of Exporter: modbus.yml \n --- \n module: VendorXY \n - temperature_a: 40001 \n - temperature_b: 40002

Exporter->Modbus_TCP_10.0.0.5: tcp://10.0.0.5?unit=10&register=40001
Modbus_TCP_10.0.0.5->Modbus_RTU_10: rtu://_?register=40001
Modbus_RTU_10-->Modbus_TCP_10.0.0.5: value=20
Modbus_TCP_10.0.0.5-->Exporter: value=20

Exporter->Modbus_TCP_10.0.0.5: tcp://10.0.0.5?unit=10&register=40002
Modbus_TCP_10.0.0.5->Modbus_RTU_10: rtu://_?register=40002
Modbus_RTU_10-->Modbus_TCP_10.0.0.5: value=19
Modbus_TCP_10.0.0.5-->Exporter: value=19

Exporter-->Prometheus:temperature_a{module="VendorXY",sub_target="10"} 20 \ntemperature_b{module="VendorXY",sub_target="10"} 19

Building

Getting Started

The modbus exporter needs to be passed the target and module as parameters by Prometheus, this can be done with relabelling (seeprometheus.yml).

Once Prometheus is properly configured, run the exporter via:

./modbus_exporter [flags]

Supported flags:

Usage of ./modbus_exporter: -config.file string Sets the configuration file. (default "modbus.yml") -modbus-listen-address string The address to listen on for HTTP requests exposing modbus metrics. (default ":9602") -telemetry-listen-address string The address to listen on for HTTP requests exposing telemetry metrics about the exporter itself. (default ":9011")

Configuration File

Check out modbus.yml for more details on the configuration file format.

TODO


Support for serial modbus was dropped in git commit d06573828793094fd2bdf3e7c5d072e7a4fd381b.