Analysis of Surface Flashover of 33k V Pin Typ e (original) (raw)
2010
Abstract
Contamination-driven insulator failure is a problem that incessantly plagues distribution systems. Contamination levels can continue to grow unless abated by natural cleaning or if not taken measures to wash insulators at the distribution level in a preventative maintenance mode. In order to assess the pollution behavior, 33kV pin type insulator was selected as a sample insulator and been subjected for natural pollution at three selected localities (zone 1, 2 and 3) for considerable period. The naturally polluted insulators have been subjected for conductivity test and by which the equivalent salt deposit density (ESDD) is calculated. Subsequently, artificially contaminated insulators of different pollution severities were tested for power frequency and impulse test in the High Voltage Laboratory of University of Moratuwa. Finally, it is recommended that insulators in Zone 1 have to be treated after 8 months from the date of last treatment and those in Zone 2 & 3 to be treated after...