Latent Heat Flow (original) (raw)

Latent heat is the heat when supplied to or removed from air results in a change in moisture content - the temperature of the air is not changed.

Latent Heat Flow - English (Imperial) units

The latent heat flow due to moisture in air can be expressed in English (Imperial) units as

Ql = 60 hwe ρ q Δx (1)

where

Ql = latent heat flow (Btu/hr)

hwe = 1060 - latent heat of vaporization of water (Btu/lb)

ρ = 0.075 - air density at standard conditions (lb/ft3 )

q = measured air flow (ft3 /min)

Δx = difference in humidity ratio (lbh2o /lbdry_air )

Latent Heat Flow - SI-Units

The latent heat flow due to moisture in air can be expressed in SI-units (metric) as

Ql = hwe ρ q Δx / 3600 (2)

where

Ql = latent heat flow (kW)

hwe = latent heat of vaporization of water ( 2454 kJ/kg - in air at atmospheric pressure and 20 oC)

ρ = air density at standard conditions ( 1.202* kg/m3 )

q = air flow (m3 /hr)

Δx = difference in humidity ratio ( kgh2o /kgdry_air )

*Note that properties of air changes with temperature. Interpolate values if necessary.

Example - Latent Heat Flow

A ventilation system transports 10000 m3 /h of air through a building.

The state of the make-up (supply) air is 0 oC and 100% relative humidity. From the Mollier diagram the humidity ratio - x - can be estimated to 0.0037 ( kgh2o /kgdry_air ) .

The state of the room air is 20 oC and 40% relative humidity. From the Mollier diagram the humidity ratio can be estimated to 0.0057 ( kgh2o /kgdry_air ) .

The latent heat flow can be calculated as

Ql = (2465.56 kJ/kg) (1.202 kg/m3 ) (10000 m3 /h) (( 0.0057 (kgh2o /kgdry_air ) ) - ( 0.0037 ( kgh2o /kgdry_air ) )) / 3600

= 16.5 kW

Moist and humid air calculations. Psychrometric charts and Mollier diagrams. Air-condition systems temperatures, absolute and relative humidities and moisture content in air.

Online calculator, figures and tables showing density, specific weight and thermal expansion coefficients of air at temperatures ranging -100 to 1600 °C (-140 to 2900 °F) at atmospheric and higher pressure - Imperial and SI Units.

The mass of water vapor present in moist air - to the mass of dry air.

Air heating buildings - heat supply vs. air flow and temperature.

Latent and sensible cooling and heating equations - imperial units.

Latent and sensible cooling loads to consider when designing HVAC systems.

The Great Sensible Heat Factor is the ratio sensible to total heat in a cooling coil.

Classification of heat recovery efficiencies - temperature efficiency, moisture efficiency and enthalpy efficiency - online heat exchanger efficiency calculator.

Enthalpy change and temperature rise when heating humid air without adding moisture.

Latent heat of vaporization for fluids like alcohol, ether, nitrogen, water and more.

Melting and boiling point temperatures, latent heat of evaporation, and melting heat of common substances like copper, gold, lead and more - SI units.

Sensible and latent heat of moist air.

Latent heat with vaporized propane.

Calculating heat removed with air by measuring the wet bulb temperature.

Room Sensible Heat Factor - RSHF - is defined as the sensible heat load divided by the total heat load in a room

Steam table with sensible, latent and total heat, and specific volume at different gauge pressures and temperatures.

Saturated Steam Table with properties like boiling point, specific volume, density, specific enthalpy, specific heat and latent heat of vaporization.

Sensible heat is dry heat causing change in temperature but not in moisture content

The ratio Sensible Heat (or Cooling) Load to the Total Heat (or Cooling) Load.

Vapor and steam enthalpy, specific enthalpy of saturated liquid, saturated vapor and superheated vapor.

Thermal properties of water at different temperatures like density, freezing temperature, boiling temperature, latent heat of melting, latent heat of evaporation, critical temperature and more.

About the Engineering ToolBox!

Privacy Policy

We don't collect information from our users. More about

We use a third-party to provide monetization technologies for our site. You can review their privacy and cookie policy here.

You can change your privacy settings by clicking the following button: .

Citation

This page can be cited as

Modify the access date according your visit.